Cable fault location is the process of locating periodic faults, such as insulation faults in cables. In this process, mobile shock discharge generators are among the devices used.

                                     

1. Cable faults

Cable faults are damage to cables which effect a resistance in the cable. If allowed to persist, this can lead to a voltage breakdown. There are different types of cable faults, which must first be classified before they can be located. The insulation of the cable plays a significant role in this. While paper-impregnated cables are particularly susceptible to external chemical and thermal influences, in high-voltage PE or XLPE cables the polyethylene insulation of the conductor is affected, leading to partial breakdowns and cracks that" eat away” the insulation.

                                     

1.1. Cable faults Phase faults

The contact between multiple conductors generates a varying resistance.

                                     

1.2. Cable faults Sheath faults

Sheath faults are damage of the cable sheath that allows the surroundings contact with the cable screen.

                                     

1.3. Cable faults Faults due to moisture

Water penetrates into the cable sheath and contacts the conductors. Impedance changes at the fault location make measuring more difficult. The resistance usually lies in the high-ohmic range.

                                     

1.4. Cable faults Disruptions

Combination of series and parallel resistances, usually in the form of a wire break. The voltage is interrupted, i.e. Ω=∞.

                                     

2. Cable testing

To locate a fault in the cable, the cable must first be tested for faults. Cable testing is therefore usually performed first in cable fault location. During the cable test, flash-overs are generated at the weak points in the cable, which can then be localised.



                                     

3. Locating the cable fault

The measures necessary for determining fault locations can be subdivided into individual steps.

Pre-location

Pre-location is used to determine the fault distance. There are predominantly two methods for this.

Route tracing and pinpointing

Route tracing is used to determine where the faulty cable lies and pinpointing is the process of determining the exact position of the cable fault.

Cable identification

In cable identification, the faulty cables are identified from the fault-free cables at the already determined site.

                                     

3.1. Locating the cable fault Fault classification

Insulation and resistance measurement provides information on the fault characteristics. An insulation test measures the insulation resistance between conductor and screen; from the periodic measurement of resistance you can derive the absorption properties of the insulating material.

                                     

3.2. Locating the cable fault Pre-location

Pre-location is used to determine the fault distance. There are predominantly two methods for this.

                                     

3.3. Locating the cable fault Transient method

In the transient method, a breakdown is triggered at the cable fault. This effects a low-resistance short circuit for a few milliseconds. This in turn produces two travelling waves diffusing in opposite directions. These waves are reflected at the cable ends so that they then travel toward each other again in the direction of the cable fault. The waves are unable to pass the fault because of the arc produced by the short circuit, so they are therefore reflected back again as with the pulse reflection method, which due to the burning short circuit results in a reversal of polarity. There are various ways to decouple and analyse these transients.

                                     

3.4. Locating the cable fault Route tracing and pinpointing

Route tracing is used to determine where the faulty cable lies and pinpointing is the process of determining the exact position of the cable fault.

                                     

3.5. Locating the cable fault Cable identification

In cable identification, the faulty cables are identified from the fault-free cables at the already determined site.



                                     

4. Loop tests for locating faults in underground cables

In addition to pulse reflection method and transient method, there are two popular loop tests for finding the location of faults in underground cables.

                                     

4.1. Loop tests for locating faults in underground cables Murray loop test

Murray loop test employs the principle of wheatstone bridge for locating the fault. To perform this test, it is necessary to have a sound cable running alongside the faulty cable. One end of the faulted cable is connected through a pair of resistors to the voltage source. Also a null detector is connected. The other end of the cable is shorted. The circuit is shown in the figure at right. The bridge is brought to balance by changing the values of R B1 and R B2. Then the distance to the fault location is calculated by solving the bridge equation. See also: Murray loop bridge

                                     

4.2. Loop tests for locating faults in underground cables Varley loop test

The similar Varley loop uses fixed resistors for RB1 and RB2, and inserts a variable resistor in the faulted leg. Test sets for cable testing can be connected for either bridge technique. If the fault resistance is high, the sensitivity of the Murray bridge is reduced and the Varley loop may be more suitable.

                                     

5. Fault conversion

After the cable fault is identified and located, it is then possible to" burn it in” using burner devices, in other words to convert it from a high-impedance fault to a low-impedance fault. For this a Burn Down Instrument, such as Baur ATG2 Burn Down Transformer or a similar device, can be used. A Burn Down Instrument has a Voltage Generator connected via Transformer and allows individual control of output voltage and current, a vital step for burning down High Impedance Faults.

                                     

6. Cable test van

The conventionally used aid in cable fault testing and location is the cable test van. The van is installed with conventional cable measuring systems for quickly reaching the location of any cable fault. In 20 years that followed, over 2000 fault location vehicles were manufactured, more than half of which were intended for the former USSR. These methods of cable fault location quickly became established in Western Europe as well.

                                     
  • to the cable Fault location is done by listening for the sound of the discharge at the fault While this test contributes to damage at the cable site
  • A shielded cable or screened cable is an electrical cable of one or more insulated conductors enclosed by a common conductive layer. The shield may be
  • the capital. At the entrance to the cable car going up to Monserrate, the fault shows reverse and normal offset faults and produced fractures in the shales
  • central location using radio or cellular signals. Typically fault indicators sense magnetic field caused by current flows through a conductor or cable Some
  • Singapore due to an unknown cable fault In August 2017, a fault in IMEWE India - Middle East - Western Europe undersea cable near Jeddah, Saudi Arabia
  • A shunt fault is a type of fault that occurs in submarine communications cables Many such cables use underwater repeaters or amplifiers to boost signals
  • pair on the affected side, if available, or identify and repair the cable fault location WLR3 Training Pack - What are all the bits between the exchange